Voltage Drop Calculator
Estimate voltage drop in volts and percent from load, one-way length, wire size, and copper or aluminum. Single phase and three phase.
Single phase or three phase, copper or aluminum, in feet or meters. A planning estimate you can cite, then send as an Invoice Mama quote.
A 120 V single-phase circuit at 20 A, 100 ft one way, on 12 AWG copper drops 7.92 V. That is 6.6% of 120 V, so 112.08 V reaches the load. The single-phase formula is VD = 2 × I × R × L ÷ 1,000. R is 1.98 ohms per 1,000 ft from NEC Chapter 9, Table 8, so VD = 2 × 20 × 1.98 × 100 ÷ 1,000 = 7.92 V.
This is a planning estimate, not code advice. It uses DC resistance only, so it leaves out reactance, power factor, and temperature correction. Check the NEC or CEC edition adopted where you work, and round up the conductor size for the final design.
How to calculate voltage drop
Three steps, the same order as the calculator above
- 1
Enter voltage, amps, and length
Type the system voltage, the load in amps, and the one-way length. Switch the length between feet and meters. Meters convert with × 3.28084 before the formula runs.
- 2
Choose size, metal, and phase
Pick a common size from 14 AWG to 1000 kcmil, copper or aluminum, and single phase or three phase. Resistance is the uncoated stranded value from NEC Chapter 9, Table 8 at 75°C.
- 3
Read volts, percent, and the guide
The result shows voltage drop, drop as a percent of system voltage, and voltage at the load. At 3% or below, the status stays within the branch guide. Above 3% and at or below 5%, it is over the branch guide and within the total guide. Above 5%, it is over the total guide.
Voltage drop formulas
Every result on this page uses these equations
Result | Formula |
|---|---|
| Single phase (V) | 2 × I × R × L ÷ 1,000 |
| Three phase (V) | √3 × I × R × L ÷ 1,000 |
| Drop percent | (VD ÷ system voltage) × 100 |
| Voltage at the load | System voltage − VD |
| Meters to feet | Length × 3.28084 |
I is the load in amps. R is DC resistance in ohms per 1,000 feet. L is the one-way length in feet. The 2 in the single-phase formula covers the outgoing and return conductors. Three phase uses √3 instead of 2.
Conductor resistance from NEC Table 8
Uncoated stranded conductors, DC ohms per 1,000 feet at 75°C
Size | Copper (Ω/1,000 ft) | Aluminum (Ω/1,000 ft) |
|---|---|---|
| 14 AWG | 3.14 | 5.17 |
| 12 AWG | 1.98 | 3.25 |
| 10 AWG | 1.24 | 2.04 |
| 8 AWG | 0.778 | 1.28 |
| 6 AWG | 0.491 | 0.808 |
| 4 AWG | 0.308 | 0.508 |
| 3 AWG | 0.245 | 0.403 |
| 2 AWG | 0.194 | 0.319 |
| 1 AWG | 0.154 | 0.253 |
| 1/0 AWG | 0.122 | 0.201 |
| 2/0 AWG | 0.0967 | 0.159 |
| 3/0 AWG | 0.0766 | 0.126 |
| 4/0 AWG | 0.0608 | 0.100 |
| 250 kcmil | 0.0515 | 0.0847 |
| 300 kcmil | 0.0429 | 0.0707 |
| 350 kcmil | 0.0367 | 0.0605 |
| 400 kcmil | 0.0321 | 0.0529 |
| 500 kcmil | 0.0258 | 0.0424 |
| 600 kcmil | 0.0214 | 0.0353 |
| 750 kcmil | 0.0171 | 0.0282 |
| 1000 kcmil | 0.0129 | 0.0212 |
Resistance values are the uncoated stranded DC ohms per 1,000 feet at 75°C from NEC Chapter 9, Table 8 (2017 edition). Solid-conductor rows and the coated-copper column are not used.
The 3% and 5% guide
A planning check, not a pass-fail rule
A common planning guide is 3% on a branch circuit and 5% for the feeder and branch together. At 3.0% or below, this page does not flag the run. Above 3% and at or below 5.0%, it flags the branch guide and still sits inside the total guide. Above 5%, it flags the total guide. The worked example is 6.6%, so it is over both lines. Treat the flags as a reason to look at a larger conductor, a shorter run, or a higher voltage, then confirm the code that applies on the job.
What this estimate leaves out
Read this before you buy wire
The math uses DC resistance only. It does not add reactance from NEC Chapter 9, Table 9, and it does not apply a power factor. It does not correct resistance for a temperature other than 75°C. Compact or coated conductors can differ from these rows. 14 AWG aluminum is listed because Table 8 has a stranded resistance for it. Whether that size is allowed on the job is a code question, not a result this calculator decides. Round up the conductor size for the final design.
Frequently asked questions
Formula, the 3% and 5% guide, and what the table includes
How do you calculate voltage drop?
Single phase uses VD = 2 × I × R × L ÷ 1,000. Three phase uses the square root of 3 instead of 2. I is amps, R is ohms per 1,000 feet, and L is the one-way length in feet. A 120 V single-phase load at 20 A, 100 ft one way, on 12 AWG copper (1.98 ohms per 1,000 ft) drops 2 × 20 × 1.98 × 100 ÷ 1,000 = 7.92 V. That is 6.6%, so 112.08 V reaches the load.
What voltage drop is too high?
A common planning guide is 3% on a branch circuit and 5% for the feeder and branch combined. This calculator marks 3% or less as within the branch guide, above 3% through 5% as over the branch guide but within the total guide, and above 5% as over the total guide. Exactly 3.0% and exactly 5.0% stay on the lower side of each line. The guide is not a code ruling. Check the NEC or CEC edition adopted where you work.
How does three-phase voltage drop differ?
Three phase multiplies by the square root of 3 (about 1.732) instead of 2, because the line-to-line path is not a simple out-and-back pair. A 208 V three-phase load at 50 A, 150 ft one way, on 6 AWG copper (0.491 ohms per 1,000 ft) drops 6.378 V, or 3.07%.
Which resistance values does the calculator use?
NEC Chapter 9, Table 8, 2017 edition. The calculator uses DC resistance for uncoated stranded conductors at 75°C, in ohms per 1,000 feet, for copper and aluminum. It does not use the solid-conductor rows, the coated-copper column, reactance, power factor, or a temperature correction. 14 AWG aluminum is on that table (5.17 ohms per 1,000 ft on the 7-strand row) and is included. A 480 V three-phase load at 100 A, 200 ft one way, on 4 AWG aluminum (0.508 ohms per 1,000 ft) drops 17.598 V, or 3.67%.
Can I enter the length in meters?
Yes. The calculator converts meters to feet with × 3.28084, then uses the foot formula. 30 m is 98.4252 ft, and the drop matches the same run entered in feet.
Is this voltage drop calculator code advice?
No. It is a planning estimate for a job quote. It ignores reactance, power factor, and temperature correction, and it does not know local amendments. Check the code that applies, and round up the conductor size for the final design. When the run looks right, put the wire, labor, and permit lines on an Invoice Mama electrical quote or invoice.
Related pages for electricians
Quote the run, then bill it
- Electrical invoice templateBill labor, materials, permits, and the voltage you recorded on the job.
- Electrical quote templatePrice wire, panels, and labor before you pull the circuit.
- EV charging calculatorEstimate charge time and energy when the job includes a charger circuit.
- All calculatorsMore free Invoice Mama calculators for contractors and small businesses.
Invoice Mama helps electricians turn wire, labor, and permit lines into a quote or invoice once the drop looks right.